SKU: 36272

1336F-BRF30-AA-EN Allen Bradley AC VFD Variable Frequency Drive Repair

Industrial VFD Repair Service – Save Big and Keep Your Settings. Our services are fast and easy. Send us your failed VFD Variable Frequency Drive. We will quickly repair your faulty VFD. We provide a quick turnaround time and a high repair success rate at a low repair cost.
UpFix is NOT an authorized distributor for Allen Bradley.

Experience the most cost-effective and efficient solution for your industrial VFD issues with UpFix expert repair service. By choosing to repair your original VFD, you not only save significantly compared to the cost of buying a new unit, but you also retain all the custom programming and configurations specific to your operational needs.
  • Estimated Repair Time is 3-5 business days.
  • 2 Year Warranty
  • Real-Time Repair Tracking
  • Our service is 100% guaranteed or your money back. Order today and save!

International Shipping Available:
Ships to USA and Canada

Free shipping available at online checkout!
$535.50
Repair yours
Send your original part for repair service
$535.50
Service Price:
Options Price:
Total:
In-stock item
Send me a good working part
Description

This is a repair service for 1336F-BRF30-AA-EN Allen Bradley AC VFD Variable Frequency Drive Repair.
UpFix is NOT an authorized distributor for Allen Bradley.

Once we receive your part, our highly trained and IPC certified technicians will run tests to identify the source of the problem. We will rebuild your part, replacing not only the failed components, but all components that are usually known to fail or go bad in this part. We want to make your experience as effortless as possible. All you have to do is send your part to us. Then after receiving the part back from us, just reinstall it and you’re back in business!

Estimated Repair Time is 3-5 business days.

International Shipping Available: Ships to USA and Canada

How it works


We take pride in our work and will take it a step further and fully inspect your control board and will replace failure prone components or parts that may be failing in the future. Each part is fully tested to make sure it passes a full functional test.

Our service is 100 percent guaranteed or your money back. We stand by our services, thats why we got you covered with a 24-month warranty and lifetime phone support when you need us

Our goal is to save you hundreds of dollars, while continuing to provide an eco-friendly solution that reduces pollution. We drive our business towards consistent and profitable growth, with integrity and a commitment to the people and communities where we live and work. Our service is 100% guaranteed or your money back.




This repair service will fix these issues:

  • Auto Tune Failure
  • Checksum Fault
  • Does Not Enable
  • Does Not Power
  • Fails Under Load
  • Fans Not Turning On
  • Ground Fault
  • Heatsink Fault
  • I/O Terminal Not Working
  • Input Phase Fault
  • Keypad Issue
  • Keys Dont Press
  • No Output
  • Output Phase Fault
  • Output Runs Erratically
  • Overcurrent Fault
  • Overvoltage Fault
  • Power Loss
  • Undervoltage Fault
  • Unit Had Blown Up
  • Unit Smoked



Cost-Effective
Repairing your existing VFD can be substantially more affordable than purchasing a new one. Enjoy significant savings while maintaining optimal functionality.

No Reconfiguration Needed
One of the biggest advantages of repairing your original VFD is the elimination of reprogramming. Your VFD will be returned to you with all its original settings intact, ensuring a seamless reintroduction into your system without the need for costly and time-consuming reconfiguration.

Quick Turnaround
We understand the importance of minimizing downtime. Our skilled technicians ensure a quick and efficient repair process, getting your operations back up and running in no time.

Quality Assurance
We use only the highest quality parts and the latest techniques in our repair processes, ensuring your VFD returns to you in top-notch condition, often better than its pre-fault state.

Extended Life for Your Equipment
Repairing and maintaining your existing VFD can significantly extend its life, making it a sustainable choice for your business and the environment.

Expert Support
Our team of experienced technicians is well-versed in a wide range of VFD brands and models, providing you with knowledgeable support and advice every step of the way.

Our Commitment
At UpFix, we are committed to providing you with a reliable, high-quality repair service that keeps your operations smooth and efficient. Trust us to restore your VFD to its optimal performance, ensuring your business runs uninterrupted.
Will this service fix my problems?

A full diagnostic check should first be performed to eliminate all other possible causes for your symptoms, even if the symptoms match those specified on the common fault description.

If you send a unit in good working condition due to misdiagnosis, and our testing determines that there are no issues or faults with the unit, or if the part is beyond repair, then you will only be responsible for the shipping costs and a bench test fee of $39.99 may be applied.

IMPORTANT! If you are not sure that this part is the cause of the fault then we recommend that you do not go ahead with this purchase and instead seek further professional advice and diagnosis.


Benefits of using us:
  • Free round trip shipping
  • Fast & easy process
  • High quality components
  • 100% guaranteed or your money back
  • Save hundreds of dollars
  • Amazing customer service and support
  • No programming needed
  • Plug-n-play
  • Refurbished and tested to meet manufacturers specifications
  • IPC certified technicians (highest standard of quality craftsmanship)
  • Hassle-free warranty that is much better than the warranties you get for new replacements.
Warranty

Warranty

Our service is 100 percent guaranteed or your money back.

For a full 24 months, our no-hassle warranty covers the repair. We will fix the item again if the repair fails within 24 months. If the component is not repairable, we will, at our discretion, either replace the part entirely or refund the cost of the repair.

We stand by our services – If the part is going to fail, itll fail within the first 3 months. Thats why we got you covered with a 24-month warranty and lifetime phone support when you need us

How It Works

How it works

Our services are fast and easy. Reducing downtime is extremely important to us. Our standard repair is usually under 1 week. Meanwhile, offering a high-quality repair service with a focus on quick, long-lasting repairs at competitive prices.


We take pride in our work and not only fully inspecting/repairing your faulty part, but will take it a step further and will replace failure prone components or parts that may be failing in the future. Each control board is fully tested to make sure it passes a full functional test. Our service is 100 percent guaranteed or your money back.


  1. Carefully remove your part.
  2. Securely pack your part, using the correct box so that your part cannot be damaged in transit. Take special care when packing.
  3. Add item to shopping cart and check out. We will provide you with shipping label to send the part to us. You will not need to pay anything until your part is full repaired.
  4. Inside the package include: Your Name, Return Address, Phone Number.


  5. International Shipping Available
    We ship to USA and Canada
Part Numbers

1336FBRF30AAEN

Error Codes
CodeDescriptionRecommended Action
Adptr Freq Err 65The SCANport adapter that was the selected frequency reference sent a frequency greater than 32767 to the drive.Correct the problem that is causing the SCANport adapter to send the illegal frequency reference to the drive.
Auxiliary Fault 02The auxiliary input interlock is open.If Control Interface option is installed, check TB3 connections. If not installed, set [Input Mode] to “Status.”
Bgnd 10ms Over 51Microprocessor loop fault. Occurs if the 10ms background task hasn’t been run in 15 ms.Replace Main Control Board or complete drive as required.
Bipolar Dir Flt 163 Wire – Bi-polar input is the active frequency reference and direction control is not possible. 2 Wire – Run Forward or Reverse commands attempt direction control, but bi-polar input is not masked from direction control.a) Mask out direction control at bit 7 of [Direction Mask]. b) Remove or mask other direction control sources. Set bit 7 of [Direction Mask] to zero.
Blwn Fuse Flt 58If the difference between the commanded voltage and the measured voltage is greater than 1/8 of rated voltage for 0.5 seconds, then a fault will be issued indicating that the bus fuse in 30 kW (40HP) & up drives has blown.Locate cause, replace fuse.
C167 Watchdog 17Internal microprocessor fault.If there is only one occurrence, reset the fault and continue. If the fault continuously or frequently reoccurs, contact your local service representative or replace the Main Control Board.
Diag C Lim Flt 36The drive output current has exceeded the hardware current limit and the [Cur Lim Trip En] parameter was enabled.Check [Cur Lim Trip En]. Check for excess load, improper DC boost setting, DC brake volts set too high or other causes of excess current.
DSP Checksum 37There was a breakdown in communications between the DSP and main processors.Reset to factory defaults. Replace Main Control Board or Gate Driver Board.
DSP Comm Fault 27Refer to the “Description” and “Action” statements for C167 Watchdog (F17) above.Refer to the “Description” and “Action” statements for C167 Watchdog (F17) above.
DSP Protected 46Flash download included a new DSP Main Block and J14 was not installed when power was restored.Remove power from the drive. Install J14 per download kit instructions and reapply power. When transfer is complete, remove power and J14.
DSP Queue Fault 31Refer to the “Description” and “Action” statements for C167 Watchdog (F17) above.Refer to the “Description” and “Action” statements for C167 Watchdog (F17) above.
DSP Reset Fault 22Power-up has been attempted with an Open Stop contact or Closed Start contact.Check/verify wiring and contact operation.
DSP Timeout Fault 28Refer to the “Description” and “Action” statements for C167 Watchdog (F17) on page 3.3.Refer to the “Description” and “Action” statements for C167 Watchdog (F17) on page 3.3.
EE Init Read 531. Gate Drive Bd. replacement (requires re-initialization). 2. Trouble reading EEPROM during initialization.1. Reset to factory defaults & cycle input power. 2. Check all connections to Power/Driver Board. Replace board or complete drive as needed.
EE Init Value 54Stored parameter value out of range on initialization.1. Reset to factory defaults & cycle input power. 2. Check all connections to the Power/Driver Bd. Replace the board or complete drive as needed.
EEprom Checksum 66The checksum read from the EEPROM does not match the checksum calculated from the EEPROM data.1. Reset to factory defaults & cycle input power. 2. Check all wire and cable connections to the Power Driver Board. Replace Power Driver Board or complete drive as required.
EEprom Fault 32EEPROM is being programmed and will not write a new value.Check all wire and cable connections to the Main Control Board. Replace Main Control Board or complete drive as required.
Encoder Loss 60The drive has detected an error in the encoder signals at TB3, terminals 31-36. The error could be due to a: 1. Loss of 1 or more channels. 2. Loss of quadrature. 3. Loss of differential signal (A & A NOT or B & B NOT were high at the same time).Check encoder and wiring.
ERROR 1 Drive -> HIMThe HIM calculated a checksum as the file was uploaded and compared it to the HIM file checksum stored after the upload. The checksums did not match, indicating the upload was not successful and the HIM file is now corrupted.Repeat the Upload.
ERROR 1 HIM -> DriveThe HIM calculated a checksum for the file to be downloaded, then checked the EEPROM checksum of the download. The checksums did not match, indicating the file stored in the HIM is invalid and the download was not successful.Upload a valid, uncorrupted file from the source drive and then repeat the download.
ERROR 2 HIM -> DriveThe number of parameters in the HIM file is different than the number of parameters in the drive file. The smaller of the two numbers is the number of parameters downloaded. The last downloaded parameter number is displayed.Verify that the correct file is being downloaded to the correct drive, then press the Enter key. Manually reprogram the parameters whose numbers are higher than the last number downloaded or whose values were incorrect.
ERROR 3 HIM -> DriveThe file in the HIM is for a different type of drive than the drive to which it is connected (i.e. 1336 PLUS file to 1336 IMPACT drive). Downloads can only occur between like drive types.None - Download not allowed.
ERROR 4 HIM -> DriveThe value just transferred to the drive is an illegal value (out of range, too high or too low) for the parameter.Record the parameter number displayed and then press the Enter key to continue the download. Manually reprogram all recorded parameters after the download is complete.
ERROR 5 HIM -> DriveThe download was attempted while the drive was running.Stop the drive and repeat the download attempt.
ERROR 6 HIM -> DriveThe file in the HIM is for a different HP or voltage drive than the drive to which it is connected (i.e. 1336 PLUS 10 HP file to 1336 PLUS 15 HP drive).If the download is desired, press the Enter key. If not desired, press the ESCape key to end the download
Fgnd 10ms Over 52Microprocessor loop fault. Occurs if a 10ms interrupt is pending before the current interrupt is complete.Replace Main Control Board or complete drive as required.
Ground Fault 13A current path to earth ground in excess of 100A has been detected at one or more of the drive output terminals. NOTE: If ground current exceeds 220% of drive rated current, “Overcurrent Flt” may occur instead of Ground Fault.Check the motor and external wiring to the drive output terminals for a grounded condition.
Ground Warning 57A current path to earth ground in excess of 2A has been detected at one or more of the drive output terminals. See [Ground Warning].Check the motor and external wiring to the drive output terminals for a grounded condition.
Hardware Trap 18Refer to the “Description” and “Action” statements for C167 Watchdog (F17) on page 3.3.Refer to the “Description” and “Action” statements for C167 Watchdog (F17) on page 3.3.
Hertz Err Fault 29This fault indicates that there is not a valid operating frequency. It can be caused by any of the following: 1. [Maximum Freq] is less than [Minimum Freq]. 2. Skip frequencies and skip bandwidth eliminate all operating frequencies. 3. Analog input signal speed reference has been lost. See [Anlg Signal Loss] and[4-20mA Loss Sel].1. Check [Minimum Freq] and [Maximum Freq] parameters. 2. Check [Skip Freq 1], [Skip Freq 2], [Skip Freq 3] and [Skip Freq Band] parameters. 3. Check for broken wires, loose connections or transducer loss at analog inputs.
Hertz Sel Fault 30A frequency select parameter has been programmed with an out of range valueReprogram [Freq Select 1] and/or [Freq Select 2] with a correct value. If problem persists, replace Main Control Board or complete drive.
Ill Prog Input 62[Fault Data] = 98 – “3 Wire” is selected as the [Input Mode] and one or more digital inputs are programmed to “Run Reverse” (2 wire action).Reprogram the digital inputs or select “2 Wire” as the [Input Mode].
Input Phase Flt 49The DC bus ripple has exceeded the value in [Phase Loss Level].1. If the drive is operated on single-phase, the load derating level has been exceeded. 2. Check incoming power for a missing phase/blown fuse.
Load Loss Flt 20[Load Loss Detect] is set to “Enabled” and the drive output torque current was below [Load Loss Level] for a time period greater than [Load Loss time].1. Verify connections between motor and load. 2. Verify level and time requirements or disable [Load Loss Detect].
Loop Overrn Flt 23An overrun of the 2.5ms control loop has occurred.Check all connections to the Main Control Board. Replace the board or complete drive as needed.
Max Retries Fault 33Drive unsuccessfully attempted to reset a fault and resume running for the programmed number of [Reset/Run Tries].Check fault buffer for fault code requiring reset. Correct the cause of the fault and manually clear by pressing the local Stop key or cycling the TB3 Stop input.
Motor Mode Flt 24A fault has been detected originating from the Control Board.Check all connections to the Control Board. Replace the board or complete drive as required.
Motor Stall Fault 06Current remained over [Current Limit] setting (parameter 36) for more than 4 seconds.If the motor is drawing excessive current (over [Current Limit] setting), the motor load is excessive and will not allow the drive to accelerate to set speed. A longer accel time or a reduced load may be required.
Motor Thermistor 15An analog option board with thermistor input is installed and the value at the terminals is less than 60 ohms or greater than 3300 ohms.1. Verify that thermistor is connected. 2. Motor is overheated. Reduce load. 3. Thermistor is not present. Remove option board.
Mult Prog Input 61A single source input function such as Reverse/Forward (open=1st function, closed=2nd function) has been programmed to more than one input or more than one “Run Reverse” input.Reprogram one or more of the inputs to a different value.
Neg Slope Fault 35Drive software detected a portion of the volts/hertz curve with a negative slope.Check drive programming. 1. [Base Voltage] parameter must be greater than [Start Boost]. 2. If the [DC Boost Select] parameter is set to “Full Custom,” [Base Voltage] must be greater than [Break Voltage] and [Break Voltage] must be greater than [Start Boost].
Op Error Fault 11A SCANport device requests a Read or Write of a data type not supported. This will also occur if: 1. [Motor Type] is set to “Sync PM” and [Stop Mode Used] is set to “DC Brake”, or 2. [Motor Type] is set to “Sync Reluc” or “Sync PM” and [Speed Control] is set to “Slip Comp”.Check programming.
Open Pot Fault 09An external pot is connected and the common side of the pot is open. The drive generates this fault when the voltage between pot leads is greater than 3.9V DC.Check the external potentiometer circuit at TB2 for an open circuit.
Option Error 14A slot A analog option board has been installed in slot B or A slot B board has been installed in slot ARemove or relocate to proper slot.
Overcurrent Flt 12Overcurrent is detected in instantaneous overcurrent trip circuitCheck for a short circuit at the drive output or excessive load conditions at the motor.
Overload Fault 07Internal electronic overload trip.An excessive motor load exists. It must be reduced such that drive output current does not exceed the current set by the [Overload Amps] parameter
Overspeed Fault 25Not functional at time of printing.
Overtemp Fault 08Heat sink temperature exceeds a predefined value of 90° C (195° F).Check for blocked or dirty heat sink fins. Check that the ambient temperature has not exceeded 40° C (104° F). Check fan.
Overvolt Fault 05DC bus voltage exceeded maximum valueMonitor the AC line for high line voltage or transient conditions. Bus overvoltage can also be caused by motor regeneration. Extend the decel time or install dynamic brake option.
Phase U Fault 38A phase to ground fault has been detected between the drive and motor in this phase.Check the wiring between the drive and motor. Check motor for grounded phase.
Phase V Fault 39A phase to ground fault has been detected between the drive and motor in this phase.Check the wiring between the drive and motor. Check motor for grounded phase.
Phase W Fault 40A phase to ground fault has been detected between the drive and motor in this phase.Check the wiring between the drive and motor. Check motor for grounded phase.
Poles Calc Flt 50Generated if the calculated value of [Motor Poles] is less than 2 or greater than 32.Check [Motor NP RPM] and [Motor NP Hertz] programming.
Power Loss Fault 03DC bus voltage remained below 85% of nominal for longer than 500ms. [Line Loss Fault] parameter is set to “enabled.”Monitor the incoming AC line for low voltage or line power interruption.
Power Mode Fault 26The internal power mode variable received an incorrect value.Check all connections to the Control Board. Replace the board or complete drive as required.
Power Overload 64The drive rating of 150% for 1 minute has been exceeded.Reduce load.
Precharge Fault 19The precharge device was open 20ms after the end of a line loss condition or the bus charging alarm remains on for 20 seconds (precharge did not complete).See Chapter 1 for frame definitions. 1. Frames A1, A2, A3 - Check the precharge circuit. Replace the drive. 2. Frame B - Check the precharge circuit. Replace the Power Driver Bd. or complete drive as required. 3. All larger frames - Check the precharge circuit. Replace the input SCRs, SCR Firing Board, Power Driver Board or complete drive as needed.
Precharge Open 56The precharge circuit was commanded to close, but was detected to be open.See page 1–1 for frame definitions. 1. Frames A1, A2, A3 - Check the precharge circuit. Replace the drive. 2. Frame B - Check the precharge circuit. Replace the Power Driver Bd. or complete drive as required. 3. All larger frames - Check the precharge circuit. Replace the input SCRs, SCR Firing Board, Power Driver Board or complete drive as needed.
Prm Access Flt 34A communication error occurred between the microprocessor and the serial EEPROM or the DSP.Record the value in [Fault Data], then reset the fault. If this fault occurs repeatedly, contact factory.
Reprogram Fault 48The drive was commanded to write default values to EEPROM.1. Clear the fault or cycle power to the drive. 2. Program the drive parameters as needed. Important: If [Input Mode] has been changed from its original value, power must be cycled before the new value will take affect.
ROM or RAM Flt 68Internal power-up ROM or RAM tests have not executed properly. Replace Control Board or complete drive as required.
Serial Fault 10A SCANport adapter has been disconnected and the [Logic Mask] bit for that adapter is set to “1.”1. If no adapter was intentionally disconnected, check wiring to the SCANport adapters. Replace wiring, SCANport expander, SCANport adapters, Main Control Board or complete drive as required. 2. If an adapter was intentionally disconnected and the [Logic Mask] bit for that adapter is set to “1”, this fault will occur. To guard against this fault occurring, set the [Logic Mask] bit for the adapter to “0.” 3. Check HIM connection for proper seating.
Shear Pin Fault 63Programmed [Current Limit] amps has been exceeded and [Shear Pin Fault] is enabled.Check load requirements and [Current Limit] setting.
Sync Loss Fault 67Not functional at time of printing.
Temp Sense Open 55Heat sink thermistor is open or malfunctioning.Check thermistor and connections.
Undervolt Fault 04DC Bus voltage fell below the minimum value (388V DC at 460V AC input). [Line Loss Fault] and [Low Bus Fault] set to “enabled.”Monitor the incoming AC line for low voltage or line power interruption.
UV Short Fault 41Excessive current has been detected between these two output terminals.Check the motor and external wiring to the drive output terminals for a shorted condition.
UW Short Fault 42Excessive current has been detected between these two output terminals.Check the motor and external wiring to the drive output terminals for a shorted condition.
VW Short Fault 43Excessive current has been detected between these two output terminals.Check the motor and external wiring to the drive output terminals for a shorted condition.
Models

This control board may be found in models similar to the following:

1336F-BRF30-AA-EN

 
Related products
ID15H215-E ABB Asea Brown Boveri AC VFD Variable Frequency Drive Repair
ID15H215-E ABB Asea Brown Boveri AC VFD Variable Frequency Drive Repair
$871.50
View Details
CIMR-F7U43P71F Yaskawa Electric AC VFD Variable Frequency Drive Repair
CIMR-F7U43P71F Yaskawa Electric AC VFD Variable Frequency Drive Repair
$599.76
View Details
22B-A5P0N204 Allen Bradley AC VFD Variable Frequency Drive Repair
22B-A5P0N204 Allen Bradley AC VFD Variable Frequency Drive Repair
$167.04
View Details
20BD022A3AYNANC1 Allen Bradley AC VFD Variable Frequency Drive Repair
20BD022A3AYNANC1 Allen Bradley AC VFD Variable Frequency Drive Repair
$1,558.15
View Details
×
1336F-BRF30-AA-EN Allen Bradley AC VFD Variable Frequency Drive Repair
1 image
  • 1336F-BRF30-AA-EN Allen Bradley AC VFD Variable Frequency Drive Repair image
1 guide
×
Contact Us